Home › Drainage fall calculator

Drainage fall calculator

In short

  • Tell it what the pipe carries, the pipe size and the run.
  • It shows the fall (1 in X), the drop per metre and the total drop.
  • Then it checks it against the minimum gradients in Approved Document H.
What does the pipe carry?
Pipe size (inside diameter)
Is a toilet (WC) connected to this run?
How many toilets in total?

Only matters for 150mm pipes.

WCs
How long is the run?

Measure along the pipe from one end to the other.

metres
What do you know?
How much lower is the far end?

Invert to invert: the bottom inside of the pipe at each end.

mm
Gradient: 1 in …

For example 40 for 1:40.

250mm drop 10m run 1 in 40
Not to scale. The far end is lower by the drop shown.

Drop per metre at common gradients

GradientDrop per 1mDrop over 10m
1 in 4025mm250mm
1 in 5020mm200mm
1 in 6016.7mm167mm
1 in 8012.5mm125mm
1 in 10010mm100mm
1 in 1506.7mm67mm
1 in 2005mm50mm

Drop per metre = 1,000 ÷ X for a gradient of 1 in X.

Where the minimums come from

  • Approved Document H1, Table 6 (foul drains): under 1 litre a second, 75mm and 100mm at 1:40; over 1 litre a second, 75mm at 1:80, 100mm at 1:80 (at least 1 WC) and 150mm at 1:150 (at least 5 WCs).
  • H1 paragraph 2.33: a foul drain should be at least 75mm; a drain taking a WC at least 100mm. Paragraph 2.19: lay pipes to even gradients.
  • H3 paragraph 3.15 (rainwater drains): 75mm and 100mm not flatter than 1:100; 150mm not flatter than 1:150.
  • H2 paragraph 1.40: drainage field pipes at a uniform gradient no steeper than 1:200. H2 paragraph 1.22: the last 12m into a septic tank can be laid at 1 in 50 or flatter to slow the flow.

Guide only, not a certified design. Figures from Approved Document H (2015 edition). Building control, or your designer, has the final say. Nothing you type here is sent anywhere.